3-4 Command Parameter List
3-26
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-S) -
Communicating with the FD-S series
3
For the communication methods using motion command parameters, see "Issuing
a Motion Command to a Sensor Amplifier" (page 3-20).
Attribute R: Read; C: Motion command
nn: ID number of sensor amplifier. Example: For nn05h and ID13, then 0D05h.
Setting/status command parameters
For the communication methods using setting/status parameters, see "Reading/
Writing Settings or Status of a Sensor Amplifier" (page 3-21).
Attribute R: Read; W
: Write; R/W: Read/Write
nn: ID number of sensor amplifier. Example: For nn41h and ID13, then 0D41h.
The data type is DINT (32-bit singed integer).
Data
category
(HEX)
Data
number
(HEX)
Name Description Attribute
00
nn00 Group-0 entry count FD-SA*A:6, FD-SA*:5 R
nn01 Zero adjustment request Executes zero adjustment. C
nn02
Integrated fl ow quantity reset
request
Resets integrated fl ow quantity.
C
nn03
Instantaneous fl ow hold value
reset request
Resets instantaneous fl ow hold value.
C
nn04
Temperature hold value reset
request
Resets temperature hold value.
C
nn05 Initial reset request (ALL)
Resets all settings of the sensor amplifi er to
the factory default settings.
C
nn06 Initial reset (SLct)
Resets the sensor amplifi er to the factory
default settings., except for some items such
as zero adjustment.
Available only to FD-S (version A).
C
Data
category
(HEX)
Data
number
(HEX)
Name
Description Attribute Sensor head
Default
value
Parameter range
00
nn20
Group-1 entry
count
R-21
nn21 Error state *1 R - -
Bit 0: Always 0
Bit 1: Head connection error
Bit 2: Overcurrent Error
Bit 3: EEPROM Error
Bit 4: Dry water error
Bit 5: Backflow error
Bits 6 - 8: Always 0
Bit 9: Drive gain error
Bit 10: Temperature lower error
Bit 11: Temperature high error
Bits 12 to 15: Always 0
nn22 to
nn23
System reserved
nn24
Output terminal
state
*2 R - -
Bit 0: Output 1
Bit 1: Output 2
Bit 2: Output 3
Bits 3 to 15: Always 0
Komentáře k této Příručce