3-2 I/O Communication
3-17
3
Communicating with the GT2 series
- DeviceNet Compatible Network Unit DL-DN1 Users Manual (GT2) -
Entering an external input into a sensor amplifier
Available external inputs: PRESET, TIMING, RESET, ERROR CLEAR
Device assignments: "External input" (page 3-11)
This example illustrates how to enter a TIMING input into the sensor amplifier of ID01.
It assumes that the operating mode assigned to the device is 3-output mode.
(1) The device value in the OUT area which is assigned an external input request is linked via I/
O communication, so that the external input of the sensor amplifier is turned on or off.
(2) The input status of the sensor amplifier can be checked with the external input response.
Set the simultaneous input setting of the sensor amplifiers to individ-
ual input. If it set to simultaneous input, the simultaneous input func-
tion becomes invalid or unable to handle the external input correctly.
When using the TIMING input, set the "timing type" of the sensor
amplifier to "external timing input."
PLC
(1)
External Input request
OUTarea [m+1]Bit0
(2)
External Input response
IN
area
[n+5]Bit0
Sensor amplifier
External Input
TIMING input to ID 01
1
0
ON
OFF
1
0
Point