4-3
4
Specifications
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (IB) -
4-2
Data Processing Time
This section describes the length of time that lasts from detection by a sensor to data
processing by PLC.
Maximum data processing time = (1) + (2) + (3) + (4)
(1)PLC scan time
(2)RPI (Transmission cycle)
(3)DL-EP1 data communication time
(4)Sensor amplifier response time
(2)RPI is set with the scanner unit. It can be set in 0.5 ms increments between 0.5 ms
and 10000 ms.
(3)DL-EP1 data communication time
The time required for sending outputs and current value data from a sensor
amplifier to the DL-EP1 is as follows:
For details on the PLC scan time in (1) and the sensor amplifier response time in (4),
refer to the manual of each unit.
Number of connected sensor
amplifiers
Output, judgment value, or
current value
1 7.8 ms
2 9.8 ms
3 13.8 ms
4 15.8 ms
CPU unit
EtherNet/IP
scanner
DL-EP1 Sensor amplifier
(1) (2) (3) (4)