Chapter 4 Use of Data Processing Functions
4
67
Flicker mode
When the power is turned ON or the hold-reset signal is input, the display
shows "----" until the first measured value is determined.
The internal timing signal is input once at every flicker time and the measured
value at the instant is displayed/output.
Average measurement function [b-2]
Calculates the average of the measured values during a specified period (sampling
period).
For the average measurement function, you can select the method to specify the
timing by the combination of the trigger mode and delay time.
For the details of the trigger mode and delay time, refer to pages 69 and 70.
Timing diagram
External trigger mode
The sampling period is between the UP edge of the hold-reset input and the UP
edge of the next timing input.
The value measured at the instant when the timing input turns ON is displayed/
output.
Reference: To start the measurement again, short-circuit the hold-reset and GND
terminals.
(t)
0
ON
OFF
Flicker
time
Displayed value
Internal timing
Intermittent
measurement value
(t)
0
ON
OFF
ON
OFF
When the power is turned ON or the hold-reset signal is input,
the display shows " " until the first timing signal is input.
Displayed value
Hold-reset input
Timing input
Average measurement value