Parameters of Commands and Responses
Data numbers
Specify the data number using three digits (ASCII characters).
z Read-only data
The following table lists the types of data that can be read from the IB Series sensor amplifiers.
Writing read-only data results in a communication error (error number: 22).
Data No. Data name Data format
*1
No. of
bytes
Attribute
*2
Data range
033 Error status*
3
***** 5 R 0 to 65535
034 Warning status ***** 5 R
0: Check output OFF
1: Check output ON
(When N.O.)
035 Warning function operating state ***** 5 R
0: Check output function disabled
1: Check output function enabled
036 Judgment output/Check output*
4
** 2 R 0 to 15
037 Judgment value (P.V.)*
5
±***.**
*6
7 R -999.99 to +999.99
038 Internal measurement value (R.V.)*
5
±***.**
*6
7 R -999.99 to +999.99
039 Peak-hold value in hold mode*
5
±***.**
*6
7 R -999.99 to +999.99
040 Bottom-hold value in hold mode*
5
±***.**
*6
7 R -999.99 to +999.99
042 Analog output value
±*.***
or
**.**
5 or 6 R
Analog voltage output:
-5.000 to +5.000*
7
Analog current output
04.00-20.00*
7
043 Bank status * 1 R 0 to 3
044 Timing status * 1 R
0: Sampling
1: Not sampling
050 Laser emission stop status * 1 R
0: Emitting
1: Emission stopped
051 Abnormal setting*
8
*1R
0: Normal setting
1: Abnormal setting
052 External input status ** 2 R 0 to 15*
9
053 EEPROM writing result*
10
*1R
0: Writing
1: Normal termination
2: Abnormal termination
054 Zero shift execution result*
11
*1R
0: Executing
1: Normal termination
2: Execution impossible
055 Reset execution result * 1 R
0: Executing
1: Normal termination
2: Execution impossible
056 System parameter current state*
11
** 2 R
Main unit: 0 to 9
Expansion unit: 0 to 1
058 Reference light registration result * 1 R
0: Executing
1: Normal termination
2:Reference light amount registration
error 1 (insufficient light amount error)
3:Reference light amount registration
error 2 (ambient light error)
059 Adjust result * 1 R
0: Executing
1: Normal termination
2:Adjust error 1 (insufficient light amount
error)
3: Adjust error 2 (ambient light error)
4: Adjust error 3 (excessive light amount
error)
060 Tuning result * 1 R
0: Executing
1: Normal termination
2: Execution impossible
Point
Parameters of Commands and Responses
*1 In the Data format column, "±" indicates that the value can be either "+" or "-" and "*" signifies a
number from "0 to 9".
*2 R: Indicates that the data type can only be read from the sensor amplifiers.
*3 You can read data number "033" to check the error status of the sensor amplifiers.
Convert the 5-digit number (ASCII characters) read to a binary number and check the ON/OFF
state of each bit to check the error.
For information on each error, refer to "IB Series User's Manual".
When the read data is "00033":
"33" is converted to the binary number "0000 0000 0010 0001".
Therefore, "Receiver error" and "Overcurrent error" have occurred simultaneously at
the sensor amplifier from which data was read.
If no error has occurred at the sensor amplifier, the data "00000" is returned.
*4 You can read data number "036" to check the judgment output status.
061 Correction result*
12
*1R
0: Executing
1: Normal termination
2: Execution impossible
193 Product code **** 4 R
Main unit: 4020
Expansion unit: 4021
195 Transmitter head mode **** 4 R
0: When the sensor head is not
connected
or the receiver is connected
1:When IB-01 transmitter is connected
2:When IB-05 transmitter is connected
3:When IB-10 transmitter is connected
4:When IB-30 transmitter is connected
196 Receiver head model **** 4 R
0: When the sensor head is not
connected
or the transmitter is connected
1:When IB-01 receiver is connected
2:When IB-05 receiver is connected
3:When IB-10 receiver is connected
4:When IB-30 receiver is connected
Bit Sensor amplifier errors
0 Overcurrent error
1 EEPROM error
2 Head error
3 Transmitter/Receiver reverse connection error
4 Transmitter internal failure error
5 Receiver error
6 Transmitter error
7 Transmitter laser error
8 Model mismatch error
9 Reference light amount registration error
10 Adjust error
11 Amplifier communication error
Data No. Data name Data format
*1
No. of
bytes
Attribute
*2
Data range
Reference
Bit 5: Receiver error Bit 0: Overcurrent error